RLE Technologies FDS-Wi Uživatelská příručka

Procházejte online nebo si stáhněte Uživatelská příručka pro Brány / ovladače RLE Technologies FDS-Wi. RLE Technologies FDS-Wi User guide Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 2
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Serial Number
Magnetic Tape
Mount the Sensor
Sensors can transmit 100 feet in open air with limited obstructions. Wireless
sensors should be mounted off the oor. While the electronics are coated to
provide a moisture barrier against condensation, the sensor is not waterproof
and submersion in water is not recommended. To prevent transmission
interference, make sure the side of the sensor with the white RLE product label
faces away from any metal surfaces.
Mount the sensor with 0.5 inch (1.27cm)
wide double-sided adhesive tape or adhesive-
backed magnetic tape. The magnetic tape
will not disturb the electronics, and works well
if the sensor is mounted on a metallic surface.
When placed correctly, the tape allows the
sensor’s label to remain visible. The serial
number on this label is unique to each sensor,
and you will need to refer to this number
throughout the life span of the sensor. If tape
is placed over the label, the paper label will
tear and the serial number will be unreadable.
Mounting holes can be found on the sides of the enclosure, if you wish to mount
it with screws, nails, or other fasteners.
© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are
trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty, limited
liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.
Wireless Sensor Quick Start Guide
including Wi-TS and Wi-THS products
Thank you for purchasing a Falcon wireless sensor, intended for use with the
FDS-Wi. This guide describes installation and troubleshooting methods for
wireless sensors available from RLE Technologies.
If you need further assistance, please contact RLE Technologies via our website
- http://www.rletech.com/ (go to the Support link) or call us at 970.484.6510,
Option 2.
v2.0
(08/2011)
Battery
Each sensor comes equipped with a 3.6V
lithium battery, which can be replaced
as needed. The sensor will not operate
with an alkaline battery - make sure the
replacement is a 3.6V lithium cell.
The sensor is shipped with a battery pull
tab in place, which turns the device off.
Squeeze the shorter sides of the lid and
remove the sensor’s cover. To activate
the sensor, remove the protective tab to
engage the battery. Turn off the sensor by
re-inserting the tab or removing the battery.
Any time the sensor is shipped, it should either be turned off or placed in a
shielded container to prevent interference that might cause shipping problems.
The Heartbeat LED ashes once every ten seconds, and lets a user know the
device is functional.
Installation Mode Switch
The sensor has an installation mode switch - a push
button located under the label in the center of the
enclosure lid. When pressed, the sensor transmits a
data packet with a special mark in its ID eld. This
indicates which sensor is in service or being installed.
The data is processed by the FDS-Wi’s Automatic
Discovery feature. For more information regarding
the FDS-Wi and wireless sensor integration, refer to
the FDS-Wi User Guide.
This push button can also act as a reset switch for the sensor. It may need to
be pushed after the battery has been removed and reinstalled, or if the sensor
is acting erratically. Pushing the button should revive the sensor and return it to
normal operation.
Troubleshooting
The transmission range of a wireless sensor depends on the distance between
the sensor and the FDS-Wi, and the number of obstacles between the two. The
more obstructions between the devices, the weaker the signal becomes.
Do not install a wireless sensor inside a solid metal cabinet. This can interfere
with its transmission.
Battery Issues
When the protective tab is pulled to activate the battery, the metal terminal clip
on the PC board can bend slightly - not enough to see, but enough to cause
intermittent connection to the battery. If this happens, the sensor will either
Protective
Battery Tab
Heartbeat
LED
Push
Button
Zobrazit stránku 0
1 2

Shrnutí obsahu

Strany 1 - Troubleshooting

Serial NumberMagnetic TapeMount the SensorSensors can transmit 100 feet in open air with limited obstructions. Wireless sensors should be mounted of

Strany 2

operate erratically or not work at all. To x this problem:1. Remove the battery.2. Gently squeeze the battery clips toward each other, bending the

Komentáře k této Příručce